HGZT-M 50 kVA Partial Discharge Testing System with 150 kV Output and 0.1 pC Sensitivity for Power Equipment
Basic Properties
Place of Origin:
WUHAN HUBEI CHINA
Brand Name:
Huagao
Model Number:
HGWS
Trading Properties
Minimum Order Quantity:
ONE
Price:
$27,500 – $118,000
Payment Terms:
L/C,D/A,D/P
Supply Ability:
Three units (sets) are supplied per month.
Specifications
| Discharge level: | Less Than 2pc | Power supply interference: | Less Than 10pc |
| Output voltage: | Line Voltage 0-310 V, Continuously Adjustable | Output current: | Line Current 75A |
| Output waveform: | Pure Sine Wave | Output distortion rate: | ≤1.0% |
Product Description
HGZT-M Power Equipment Partial Discharge Testing System

1. Power Equipment Partial Discharge Test Control Panel HGZT-M
The installation location should be level with a slope less than 5°.
- Local discharge level (spatial interference)
- less than 2pc
- Partial discharge interference (power supply voltage source)
- less than 10pc
- Protection features
- overcurrent protection ; Breakdown and flashover protection; Zero position protection upon startup; Power failure protection; Linkage protection for the cooling fan
- System control
- enables control of both three-phase power supplies and single-phase industrial-frequency power systems
- Software functionality
- performs testing through communication with the partial discharge detector. It has a one-click feature to generate test reports. Supports third-party access and database data interaction.
2. Non-localized variable-frequency power supply TP-50
- Power supply voltage and frequency
- Three-phase 400V ±10%; 50Hz
- Power supply capacity
- greater than 50 kVA
- Rated output power
- 30 kW
- Rated output voltage
- line voltage 0–310 V, continuously adjustable (phase angle difference 120° ± 1°)
- Rated output current
- Line current 75A
- Output waveform
- pure sine wave
- Phase count
- Three-phase four-wire system
- Output waveform distortion rate
- ≤1.0%
- Output voltage instability
- ≤1.0%
- Three-phase output symmetry
- Three-phase line voltage imbalance ≤2%; The phase deviation angle difference between the three phases is ≤1.0%
- Cooling method
- Forced air cooling
- Frequency adjustable range
- 50Hz to 300Hz
- Output frequency resolution
- 0.1 Hz
- Output frequency instability
- ≤0.5%
- Noise level
- ≤80 dB
3. Non-localized discharge excitation transformer ZB3-50KW
- Rated capacity
- 50 kVA
- Input side rated voltage
- 320V
- Phase configuration
- three-phase four-wire system, YN-D
- Input side rated current
- 50A
- Rated output voltage
- 900V
- Insulation level
- Low-voltage winding to ground: 3 kV/1 min; The high-voltage winding induces a voltage of 1.2 times for 1 minute
- Rated frequency
- 50–300 Hz
- Partial discharge level
- The partial discharge quantity at rated voltage is ≤5 pC
4. No partial discharge test transformer WDJ-50KVA/150KV
- Rated capacity
- 50 kVA
- Input side rated voltage
- 400V
- Phase count
- Single-phase
- Input side rated current
- 132 A
- Output side rated voltage
- 150 kV
- Insulation level
- Low-voltage winding to ground: 5 kV/1 min; The high-voltage winding induces a voltage of 1.2 times for 1 minute
- Insulation method
- sulfur hexafluoride gas
- Rated frequency
- 50–300 Hz
- Partial discharge level
- The partial discharge quantity at rated voltage is ≤5 pC
5. No partial discharge coupling capacitor WF-300/150
- Rated voltage
- 150 kV
- Pressure rating
- 150 kV
- Operating frequency
- 50–300 Hz
- Capacitance
- C1 = 300 pF ± 5%
- Partial discharge level
- <5 pC at rated voltage
6. No partial discharge protection resistor HCWR-10/150
- Rated voltage
- 150 kV
- Rated current
- 0.2 A
- Operating frequency
- 50–300 Hz
- Resistance
- 10 kΩ ±5%
- Partial discharge level
- <5 pC at rated voltage
7. No partial discharge coupling capacitor HCWF-300/60
- Rated voltage
- 60 kV
- Pressure rating
- 60 kV
- Operating frequency
- 50–300 Hz
- Capacitance
- C1 = 300 pF ± 5%
- Partial discharge level
- <5 pC at rated voltage
8. Localized discharge power isolation filter HCF-80
- Rated voltage
- 440 V AC
- Rated current
- 80 A
- Filter frequency band range
- 10–300 kHz
- Rated capacity
- 50 kVA
- Insulation method
- Dry type
- Partial discharge level
- <5 pC at rated voltage
9. Digital partial discharge detector PD-9104
- Number of channels
- 4 independent channels
- Sampling rates
- 1M,5M, or 10M available
- Sampling accuracy
- 12-bit
- Range switching
- 6 levels-40 dB, -20 dB, 0 dB, 20 dB, 40 dB, and 60 dB
- Measurement frequency band
- 3 dB bandwidth from 10 kHz to 1 MHz
- Digital filtering
- Select from 10 kHz to 1 MHz
- Program-controlled filter segmentation
- Low-end frequencies: 10 kHz, 20 kHz, 40 kHz, 80 kHz High-frequency range: 100 kHz, 200 kHz, 300 kHz, 400 kHz
- Nonlinear error within this range
- 5%
- Measurement range
- 0.1 pC to 10,000 pC
- Sensitivity
- 0.1 pC
- Test sample capacitance range
- 6 pF to 250 µF
- Test power supply frequency range
- 50–500 Hz
10. Partial discharge test accessory PD-02
- Accessorie
- Square wave calibrator, impedance input unit, discharge rod